Cci-thermal-technologies FE2 - Explosion-Proof Electric Air Unit Heater Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Chaudière à eau Cci-thermal-technologies FE2 - Explosion-Proof Electric Air Unit Heater. CCI Thermal Technologies FE2 - Explosion-Proof Electric Air Unit Heater User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
FE 2 - 2201 50 - 025
KILOWATT RATING
HERTZ
PHASE
VOLTAGE
2nd GENERATION
MODEL SERIES
WARNING!
READ ALL IMPORTANT NOTICES
MODEL CODING
Part No. 10525.Rev.8.00 Issue Date: November 2013 Printed in Canada
Ruffneck
TM
and VacuCore
®
are registered trademarks of CCI Thermal Technologies Inc.
Copyright
©
2013. All rights reserved.
CCI Thermal Technologies Inc.
5918 Roper Road
Edmonton, Alberta
T6B 3E1 Canada
II2 G Ex d IIB T3 Gb
DEMKO 10 ATEX 0910365X
-20°C (-4°F) ≤ Tamb ≤ 40°C (104°F)
ISO 9001
FE2 Series
Electric Forced Air Heaters for Hazardous Locations
This manual covers the installation, maintenance, repair and replacement parts.
Owners Manual
POCC CA. ГБ06.B00914
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - FE2 Series

FE 2 - 2201 50 - 025 KILOWATT RATING HERTZ PHASE VOLTAGE 2nd GENERATION

Page 2 - PREVENTATIVE MAINTENANCE GRID

10FE2 TECHNICAL DATA FOR 60 HZ ELECTRIC AIR HEATERSNOTES: 1. Minimum conductor size for 30˚C (86˚F) ambient. Derate conductor for ambient

Page 3 - 1-780-466-3178 (24 hrs)

11PARTS LISTFORCED AIR ELECTRIC HEATERSFE2 PART NUMBERSITEM 2.5 - 4.6 kW 6.3 - 10 kW 12.5 - 20 kW 20.9 - 35 kW Description1 ** Core2Painted: 9203S.S.:

Page 4 - IMPORTANT NOTICES

122223Optional built-inthermostat #23 replaces item #16242526272829303132333435364243123456789101112131415161718192021See high-limitassembly diagram(b

Page 5 - TROUBLESHOOTING TIPS

13SPECIFICATIONS FOR ALL 50 HZ MODEL Nominal kW 2.5 3.7 6.3 8.4 12.5 14.9 20.9 22.4 to 3.0 to 5.0 to 7.5 to 10 to 13.

Page 6 - ELECTRICAL

14SPECIFICATIONS FOR ALL 60 HZ MODEL 2.5 3.7 6.3 8.4 12.5 14.9 20.9 22.4 Nominal kW to 3.0 to 5.0 to 7.5 to 10 to 13.

Page 7 - FINAL INSPECTION

15REPAIR & REPLACEMENT1. After repairing any component: a. check that electrical connections are correct and secure (see Figure 9), b. remo

Page 8 - FIGURE 9

16PRINTED CIRCUIT BOARD1. After removing the printed circuit board (P.C. Board) bracket assembly from the control enclosure, separate the P.C. Board

Page 9

17NOTES

Page 10

18NOTES

Page 11 - PARTS LIST

19PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL.Failure to do so may be dangerous and may void certain provisions of your warranty. For furth

Page 12 - HEATER ASSEMBLY DIAGRAM

2HEATER MAINTENANCE CHECKLISTFor Electric Forced Air HeatersHeater Model: _________________________ Serial No.: ___________________________Date of M

Page 13 -

20DIRECTIVE 2003/108/EC AMMENDMENT TO THE DIRECTIVE 2002/96/EC OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL on waste electrical and electronic equipm

Page 14

3 PERIODIC (before and as required during heating season) Remove dust using compressed air. Do not spray with water or solvents. Do not immerse in wa

Page 15 - REPAIR & REPLACEMENT

4WARNINGRead and adhere to the following. Failure to do so may result in severe or fatal injury.WARRANTY WILL BE VOIDIMPORTANT NOTICES1. Read and fo

Page 16 - FIGURE 18

5INSTALLATIONThe installation instructions provide a general guideline for the installation and wiring of the heater. All applicable local codes must

Page 17

6MAXIMUM TILT ANGLES(EITHER DIRECTION) WARNINGDisconnect heater from power supply at fuse box before opening enclosures or servicing heater. Loc

Page 18

7FIGURE 8FIGURE 7AFIGURE 6Optional factory installed built-in room thermostat.3. The internal grounding terminal in the control enclosure shall be us

Page 19

8FIGURE 9ELEMENTSOPTIONALPILOTLIGHTOPTIONALROOMTHERMOSTATPCBFUSEOPTIONALREDUNDANTTEMPERATUREHIGH-LIMITAUTO-RESETTEMPERATUREHIGH-LIMIT(AMBIENT AIR)AUTO

Page 20

9FE2 TECHNICAL DATA FOR 50 HZ ELECTRIC AIR HEATERSNOTES: 1. Minimum conductor size for 30˚C (86˚F) ambient. Derate conductor for ambient